Enclosure Cooling / Sizing
Heat inside the box, temperature outside it — that decides fans or a cooling unit.
What is in the box?
Type a part number to fill in size and clearances from ABB’s manual.
Drive size and clearances
Free space comes from the drive’s hardware manual.
Total heat inside—
Allowed rise—
—
The enclosure
Green = intake fan. Amber = exhaust.
Recommendation
—
Bill of materials
| Item | Part number | Note |
|---|
What is in the box
Allowed rise—
Sealed box would need—
—
The enclosure
Green = filtered intake fan (low, left). Amber = exhaust filter (high, right).
Blue = closed-loop cooling unit on the side.
Option 1 — filter fans
—
Option 2 — cooling unit
—
How this decides
| Check | Rule |
|---|---|
| Fans possible | Ambient must sit below the internal target with at least 3 K to work with |
| Fan size | CFM = 1.82 × watts ÷ ΔT(°C), on the installed CFM3 figure |
| Fan must fit | Fan flange + 1 in ≤ enclosure depth (fans mount on the side wall) |
| Two fans | If one cannot carry it, two of the largest that fit — one low on each side |
| Cooling unit | Net = (losses − heat the box sheds) × 1.25 |
1 W = 3.412 BTU/h. NEMA 12 / 3R / 4 / 4X use the installed, filtered figure (Pfannenberg CFM3).
A NEMA 1 box needs no filter, so it is sized on the fan’s free-air figure (CFM1) less about 15% for the
enclosure and vent — and the filter element must be taken out of the fan; left in, it runs at the
CFM3 figure and the box will overheat.