VFD Configurator

VFD Configurator

Size an ABB variable frequency drive and get the bill of materials in one pass. Enter the motor nameplate, the supply and where the drive will live. The configurator picks the drive, the frame that actually covers the load, the NEMA enclosure kit, the line reactor, the input fuses or circuit breaker, the filters and the communications card. It covers ACS180, ACS380, ACS580-01, ACQ580-01 and ACS880-01, and ACS255 for 110 V single-phase. US listings only. For pricing, call your local distributor.

ACH180 & ACH580 (HVAC) drives are not shown here yet. These pages are being updated continually, so refresh the page before sizing a drive.

Three-phase AC motor

Motor Nameplate

This motor info is just sizing the items below. The motor will not be added to the BOM.
Line reactor / filter

Output Filter

ABB VFD drive

Drive (VFD)

Line reactor / filter

Input Filter for Harmonic & line surges (Optional)

Circuit breaker

Input Protection (Short Circuit / Ground Fault)

Show alternate protection options

Your Build of Materials (BOM)

#CompanyDescriptionPart / Cat#QtyUnit

Complete the installation to generate your BOM.

How this configurator sizes a drive

Motor, supply and load

The motor nameplate sets the requirement. Enter the horsepower and, if you have it, the full-load amps from the nameplate. The nameplate FLA is more accurate than a table figure and can change the frame that gets quoted, so it is worth typing in. The supply side is the power coming out of the wall. The drive output is always three-phase, so a single-phase supply still drives a three-phase motor.

Light duty and heavy duty

Every ABB drive carries two ratings: light duty for variable torque loads such as fans and centrifugal pumps, and heavy duty for constant torque loads such as conveyors, positive displacement pumps and hoists. The configurator uses the rating that matches the application you select, which is why the same motor can quote a different frame when you switch from a fan to a constant torque load.

Two frames can share one horsepower label. ABB rates its drives in kilowatts and the US horsepower figures are a re-rating of those numbers, and the conversion does not always land cleanly. Where two frames claim the same horsepower, the current rating decides: the configurator will not quote a drive whose horsepower rating is below the motor, even when its amps would cover the load.

Altitude and temperature

Sizing is done at the altitude and ambient temperature you enter, and each drive family is derated with its own rule rather than one formula for all of them. ACS180 tops out at 2000 m. ACS380 reaches 2000 m on 230 V and 4000 m on 400 and 480 V, but the 4000 m figure applies only to TN-S and TT grounding; corner-grounded delta, midpoint-grounded delta and IT systems stop at 2000 m. ACS580-01, ACQ580-01 and ACS880-01 are rated to 4000 m and allow a temperature credit below 40 degrees C, which the micro drives do not. Above 1000 m every family derates one percent per 100 m, and the tool applies the correction to the drive that is actually quoted, not to the motor.

Enclosures and NEMA type

NEMA 1 kits are stocked for ACS180 and ACS380. ACS580-01, ACQ580-01 and ACS880-01 are already finger-safe in their standard form, so they are treated as NEMA 1 without a kit. NEMA 4X washdown is quoted as ACS580-01 only. NEMA 3R is quoted as a packaged ACS580-0P with a disconnect and fuses, or with a circuit breaker and fuses when you select that option. A drive that already carries an enclosure plus code above NEMA 1 is not put inside a second enclosure.

Reactors, filters and protection

Line reactors and harmonic filters are offered from MTE first, and from ABB when MTE has no part for that rating, with the reason shown on the line. An output filter is selected by motor cable length: nothing below about 50 ft, a 3 percent load reactor from about 50 to 100 ft, a dv/dt filter from about 100 to 900 ft, and a sine-wave filter beyond that. The input and output filter NEMA rating matches the drive enclosure where it can: an open or IP20 drive takes an open filter, a NEMA 1 or NEMA 12 drive takes the NEMA 1/2 filter, a NEMA 3R drive takes a NEMA 3R filter, and because there is no NEMA 4X filter rating, a NEMA 4X drive takes the NEMA 1/2 filter as well. For separate NEMA rated filters, use the Expert tab. Input protection is either current-limiting fuses or a circuit breaker, and each drive row carries the fuse, manual motor protector and breaker that ABB lists for that frame.

What this tool does not do

It shows part numbers, not prices. It covers US listings and the common wall-mount styles, not every variant ABB makes. It does not size 690 V drives, brake choppers, resistors, encoders, line contactors, bypass packages or flange-mount kits. Single-phase motors are out of scope because most drives do not run them. It is a personal project and a starting point for a quote, not a substitute for the ABB manual or for engineering review of the installation.